 |
OPERATING
INSTRUCTIONS
PURPOSE – For proper
operation of the Model 37HD1 & 37HD2 Backflow Preventer as installed
on a hose threaded outlet, carefully adhere to the instructions below.
PROCEDURE –
-
During normal usage the Backflow Preventer must be
turned clockwise hand tight to a seated position. See figure 1a.
- The faucet with the Backflow Preventer installed, may
be operated with or without a hose attached. See figure 1b.
- When the Backflow Preventer is installed on a
frost-proof faucet and freezing temperatures occur, shut off the water
and turn the Backflow Preventer counter-clockwise until it starts
draining, approximately 3 turns. Water will drain out of the faucet
through the drain slots provided in the Backflow Preventer. See figure
1c
- After the frost proof faucet has stopped draining, turn
the Backflow Preventer Clockwise hand tight back to a seated position.
See figure 1d. The faucet is now protected from freeze damage.
CRITERIA –
The Model 37HD1/37HD2 Backflow Preventer must be tightly
seated on all faucets in order to function properly. When freezing
temperatures occur, manual draining of frost-proof faucets must be done to
prevent freezing of the faucet and possible damage. This manual draining is
achieved by turning the Backflow Preventer as described above.
|
FIELD TEST
INSTRUCTIONS
PURPOSE – The instructions
below are intended to encourage preventative maintenance by the end user
of the Model 37HD1 & 37HD2 Backflow Preventer. These procedures shall
verify the integrity of the outlet check valve.
PROCEDURE –
- With the device installed in accordance to the
manufacturer’s instructions, attach a hose to the outlet of the
Backflow Preventer as shown in Figure 2a. Raise the hose to a height of
305-cm (10 feet). Turn on the faucet and let water run to purge the hose
of air. Turn off the faucet.
- Turn the Backflow Preventer counter-clockwise 2 turns
as shown in figure 2b, while watching the atmospheric vents for leakage.
- Turn the Backflow Preventer clockwise back to a seated
position as shown in figure 2c.
- Maintain the hose at a height of 305-cm(10 feet) for
five minutes while watching the atmospheric vents for leakage.**
CRITERIA –
*A small leakage at the atmospheric vents that does not
exceed approximately 6 seconds duration is normal and indicates proper
operation.
** Continuous leakage at the atmospheric vents that exceed
approximately 6 seconds indicates that the outlet check valve is faulty.
For continuous protection the Backflow Preventer shall
be replaced if faulty.
|